Configuring an External E-STOP Signal in CoreCubic-S
What Is E-STOP?
E-STOP (emergency stop) is one of the fundamental safety functions used in industrial robotic cells. It enables the robot or other devices within the system to be stopped in an emergency, for example, when an external emergency stop button is pressed.
The CoreCubic-S system allows an external safety signal to be assigned to the robot’s emergency stop function. A safety output can also be configured to forward information to a higher-level device, such as a Safety PLC, confirming that the motor power shutoff command has been executed.
Configuration Scope
The configuration described in this article includes:
- Assigning User Safety Input 1 to the external emergency stop function.
- Configuring User Safety Output 1 as a status signal indicating that the motor power shutoff command has been executed.
An additional Safety I/O board is required to support the safety inputs and outputs.
Configuring E-STOP using the Teach Pendant
Adding a Safety I/O Board
Adding a Safety I/O board enables the usage of safety inputs and outputs in the CoreCubic-S system. The value specified in the configuration must correspond to the number of Safety I/O boards physically installed in the controller.
Go to menu:
TEACH → CCS (Core Cubic-S) → Status → System

In the Safety I/O Boards field, set the value to: 1. Cofirm the configuration by clicking the “Update” button.
Assigning an Input to the E-STOP Function
Assigning the safety input enables the signal from User Safety Input 1 to be used as an external emergency stop signal.
Go to menu:
Signal Settings → Logical Operation
In the LogicOP Result No. field, enter: 1.
Then configure the first logical operation:
OP: Thru
IN1: User Safety Input (1)
Assign: SW External Emergency Stop

The Thru operation transfers the state of the specified input without performing any additional logical operations. In this configuration, the state of User Safety Input 1 is assigned directly to the SW External Emergency Stop function.
The SW External Emergency Stop signal provides the external emergency stop function within the system software. The close circuit state enables operation, while the open circuit state triggers an emergency stop.
Configuration of the emergency stop status output
Functions can also be assigned to output signals. To the output, a function informing the controller that the robot’s motors have been stopped will be assigned. This can be used as a status signal in the Safety PLC.
In the LogicOP Result No. field, enter: 2.
Then configure the second logical operation:
OP: Thru
IN1: Motor Power Shutoff Command Performed 1 (2001)
Assign: User Safety Output 1

In this configuration, the state of the Motor Power Shutoff Command Performed 1 (2001) signal is transferred to User Safety Output 1.
This output can be used to transmit information about the safety system status to an external device, such as a Safety PLC. Signal 2001 uses the following logic: the ON state indicates that the motor power shutoff command has not been executed, while the OFF state indicates that the command has been executed.
Updating the Settings
After configuring the individual parameters, select Update.
The Update function applies to the parameter changes in the configuration application but does not save them to the CoreCubic-S system. An additional write operation is required to transfer the configuration to the safety system.
Writing the Configuration to CoreCubic-S
Go to menu:
CoreCubic-S → Write CoreCubic-S
Enter the user password.
The Write CoreCubic-S function saves the configured parameters to the CoreCubic-S system.
Once the write process has started, do not close the application until a message confirming its successful completion is displayed.
Restarting the Controller
After the parameters have been written successfully, reboot the robot controller..
A controller restart is required for the new safety parameters to take effect in the CoreCubic-S system. If the controller is not restarted, a message may be displayed indicating that the safety parameters have been changed and that a power cycle is required.
After restarting the controller, verify the correct operation of the external E-STOP signal and the status output.