{"id":804,"date":"2018-09-04T10:04:28","date_gmt":"2018-09-04T08:04:28","guid":{"rendered":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/?p=804"},"modified":"2020-04-16T15:54:06","modified_gmt":"2020-04-16T13:54:06","slug":"jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp","status":"publish","type":"post","link":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\/","title":{"rendered":"Jak po\u0142\u0105czy\u0107 sterownik PLC firmy Horner z panelem operatorskim Astraada HMI za pomoc\u0105 protoko\u0142u Modbus TCP?"},"content":{"rendered":"\n<div class=\"dowiesz-sie\">\n<h3>Z tego artyku\u0142u dowiesz si\u0119:<\/h3>\n<ul class=\"bulleted\">\n<li>Jak skonfigurowa\u0107 sterownik Horner (SLAVE)<\/li>\n<li>Jak skonfigurowa\u0107 Astraada HMI (MASTER)<\/li>\n<li>Jak stworzy\u0107 przyk\u0142adow\u0105 aplikacj\u0119<\/li>\n<\/ul>\n<\/div>\n\n\n\n<div style=\"height:20px\" aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n\n\n\n<center><figure><iframe loading=\"lazy\" src=\"https:\/\/www.youtube.com\/embed\/MqM8dcYKajI?rel=0\" width=\"830\" height=\"467\" frameborder=\"0\" allowfullscreen=\"allowfullscreen\"><\/iframe><\/figure><\/center>\n\n\n\n<p class=\"text-main\"><span style=\"color: #333333;\">Konfiguracji dokonujemy przez program Cscape dla <a href=\"https:\/\/www.astor.com.pl\/produkty\/sterowanie\/sterowniki-plc-z-panelem.html\" target=\"_blank\" rel=\"noreferrer noopener\" aria-label=\"sterownika Horner (opens in a new tab)\">sterownika Horner<\/a> oraz <a href=\"https:\/\/www.astor.com.pl\/produkty\/sterowanie\/panele-operatorskie\/astraada-hmi-panel.html\">Astraada HMI<\/a> CFG dla panelu Astraada HMI. Przed rozpocz\u0119ciem konfiguracji nale\u017cy si\u0119 upewni\u0107, \u017ce urz\u0105dzenia pracuj\u0105 w tej samej podsieci i maj\u0105 r\u00f3\u017cny numer IP.<\/span><\/p>\n\n\n\n<div style=\"height:35px\" aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n\n\n\n<h2 class=\"wp-block-heading\">Konfiguracja sterownika Horner (SLAVE)<\/h2>\n\n\n\n<p class=\"text-main\">W pierwszym kroku nale\u017cy utworzy\u0107 nowy projekt w \u015brodowisku <a href=\"https:\/\/www.astor.com.pl\/produkty\/sterowanie\/oprogramowanie-narzedziowe\/cscape.html\" target=\"_blank\" rel=\"noreferrer noopener\" aria-label=\"Cscape (opens in a new tab)\">Cscape<\/a> i zapisa\u0107 go na dysku lokalnym komputera. W celu konfiguracji urz\u0105dzenia nale\u017cy przej\u015b\u0107 do zak\u0142adki\u00a0<strong>Hardware Configuration<\/strong>.<\/p>\n\n\n\n<div class=\"wp-block-image\"><figure class=\"aligncenter\"><img loading=\"lazy\" decoding=\"async\" width=\"351\" height=\"244\" src=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_001.png\" alt=\"\" class=\"wp-image-806\" srcset=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_001.png 351w, https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_001-300x209.png 300w\" sizes=\"auto, (max-width: 351px) 100vw, 351px\" \/><\/figure><\/div>\n\n\n\n<p class=\"text-main\">W oknie Hardware Configuration, w zak\u0142adce&nbsp;<strong>Controller<\/strong>&nbsp;mo\u017cliwe jest wybranie serii, typu oraz modelu urz\u0105dzenia. Poni\u017cej znajduje si\u0119 pole port\u00f3w sieciowych (<strong>Network Ports<\/strong>) CAN oraz LAN. Nale\u017cy wybra\u0107 konfiguracj\u0119&nbsp;<strong>Config<\/strong>, tego portu LAN, z jakim b\u0119dzie przeprowadzana komunikacja.<\/p>\n\n\n\n<p class=\"text-main\">Dodatkowo w tej zak\u0142adce znajduje si\u0119 r\u00f3wnie\u017c pole w\u0142a\u015bciwo\u015bci&nbsp;<strong>Properties<\/strong>, jednak zmiany w\u0142a\u015bciwo\u015bci nie s\u0105 konieczne.<\/p>\n\n\n\n<div class=\"wp-block-image\"><figure class=\"aligncenter\"><img loading=\"lazy\" decoding=\"async\" width=\"759\" height=\"480\" src=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_002.png\" alt=\"\" class=\"wp-image-807\" srcset=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_002.png 759w, https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_002-300x190.png 300w\" sizes=\"auto, (max-width: 759px) 100vw, 759px\" \/><\/figure><\/div>\n\n\n\n<p class=\"text-main\">Po wybraniu konfiguracji portu LAN, po kt\u00f3rym si\u0119 komunikujemy pojawi si\u0119 okno.<br>\nW polu&nbsp;<strong>Register Usage<\/strong>&nbsp;konieczne jest ustawienie adresu IP urz\u0105dzenia (<strong>IP Address<\/strong>), maski sieciowej (<strong>Net Mask<\/strong>) oraz bramy (<strong>Getaway<\/strong>). W tym oknie istnieje te\u017c mo\u017cliwo\u015b\u0107 ustawienia rejestr\u00f3w.<\/p>\n\n\n\n<p class=\"text-main\">W \u015brodkowej cz\u0119\u015bci okna znajduj\u0105 si\u0119 dost\u0119pne protoko\u0142y komunikacji, nale\u017cy zaznaczy\u0107 opcj\u0119&nbsp;<strong>Modbus Slave<\/strong>. Je\u015bli jest to konieczne, mo\u017cliwa jest zmiana ustawie\u0144 protoko\u0142u przez wybranie opcji&nbsp;<strong>Configure Selected Protocol<\/strong>.<\/p>\n\n\n\n<div class=\"wp-block-image\"><figure class=\"aligncenter\"><img loading=\"lazy\" decoding=\"async\" width=\"872\" height=\"609\" src=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_003.png\" alt=\"\" class=\"wp-image-808\" srcset=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_003.png 872w, https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_003-300x210.png 300w, https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_003-768x536.png 768w\" sizes=\"auto, (max-width: 872px) 100vw, 872px\" \/><\/figure><\/div>\n\n\n\n<p class=\"text-main\">Nast\u0119pnie wprowadzone zmiany trzeba zaakceptowa\u0107 wybieraj\u0105c&nbsp;<strong>OK<\/strong>.<\/p>\n\n\n\n<div class=\"wp-block-image\"><figure class=\"aligncenter\"><img loading=\"lazy\" decoding=\"async\" width=\"479\" height=\"209\" src=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_004.png\" alt=\"\" class=\"wp-image-809\" srcset=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_004.png 479w, https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_004-300x131.png 300w\" sizes=\"auto, (max-width: 479px) 100vw, 479px\" \/><\/figure><\/div>\n\n\n\n<div style=\"height:35px\" aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n\n\n\n<h2 class=\"wp-block-heading\">Konfiguracja <a href=\"https:\/\/www.astor.com.pl\/produkty\/sterowanie\/panele-operatorskie\/astraada-hmi-panel.html\" target=\"_blank\" rel=\"noreferrer noopener\" aria-label=\"Astraada HMI (opens in a new tab)\">Astraada HMI<\/a> (MASTER)<\/h2>\n\n\n\n<p class=\"text-main\">W pierwszym kroku konfiguracji Astraada HMI w programie ASTRAADA HMI CFG konieczne jest utworzenie nowego projektu. W celu dodania nowego \u0142\u0105cza nale\u017cy klikn\u0105\u0107 prawym przyciskiem myszy w drzewie projektu na element&nbsp;<strong>Links<\/strong>, a nast\u0119pnie doda\u0107 \u0142\u0105cze przez opcj\u0119&nbsp;<strong>Add Link<\/strong>.<\/p>\n\n\n\n<div class=\"wp-block-image\"><figure class=\"aligncenter\"><img loading=\"lazy\" decoding=\"async\" width=\"228\" height=\"149\" src=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_005.png\" alt=\"\" class=\"wp-image-810\"\/><\/figure><\/div>\n\n\n\n<p class=\"text-main\">Konfiguruj\u0105c \u0142\u0105cze w zak\u0142adce&nbsp;<strong>General<\/strong>&nbsp;nale\u017cy odpowiednio ustawi\u0107 wszystkie parametry.<\/p>\n\n\n\n<p class=\"text-main\">W polu&nbsp;<strong>Link Name<\/strong>&nbsp;nale\u017cy wpisa\u0107 nazw\u0119 w\u0142asn\u0105 \u0142\u0105cza, a w polu&nbsp;<strong>Link Type<\/strong>&nbsp;(typ \u0142\u0105cza) wybieramy&nbsp;<strong>Direct Link (Ethernet)<\/strong>.<br>\nW zak\u0142adce&nbsp;<strong>Device\/Server<\/strong>&nbsp;(Urz\u0105dzenie\/Serwer) nale\u017cy wybra\u0107:&nbsp;<strong>Modicon Corp.<\/strong>&nbsp;oraz&nbsp;<strong>ModBus Device\/Slave (TCP\/IP)<\/strong>, a w polu Link Port gniazdo portu LAN s\u0142u\u017c\u0105cego do komunikacji. Zaznaczenie opcji&nbsp;<strong>Sub-links<\/strong>&nbsp;umo\u017cliwia dodanie do 8 urz\u0105dze\u0144 Slave obs\u0142ugiwanych na jednym \u0142\u0105czu.<br>\nOpcja&nbsp;<strong>Record communication status in operation log<\/strong>&nbsp;pozwala na mo\u017cliwo\u015b\u0107 rejestrowania statusu. Przy zaznaczeniu tej opcji konieczne jest w\u0142\u0105czenie zapisywania w&nbsp;<strong>Operation Logging<\/strong>.<\/p>\n\n\n\n<p class=\"text-main\">Mo\u017cliwe jest r\u00f3wnie\u017c dodanie zmiennej przechowuj\u0105cej status po\u0142\u0105czenia dzi\u0119ki zaznaczeniu opcji&nbsp;<strong>Check Word<\/strong>. W dolnej cz\u0119\u015bci okna wybieramy z listy d\u0142ugo\u015b\u0107 czasu wy\u015bwietlania komunikatu b\u0142\u0119du po\u0142\u0105czenia na ekranie HMI (<strong>The duration of showing a communication error message<\/strong>).<\/p>\n\n\n\n<div class=\"wp-block-image\"><figure class=\"aligncenter\"><img loading=\"lazy\" decoding=\"async\" width=\"682\" height=\"470\" src=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_006.png\" alt=\"\" class=\"wp-image-811\" srcset=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_006.png 682w, https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_006-300x207.png 300w\" sizes=\"auto, (max-width: 682px) 100vw, 682px\" \/><\/figure><\/div>\n\n\n\n<p class=\"text-main\">W zak\u0142adce&nbsp;<strong>Parameter<\/strong>&nbsp;nale\u017cy wpisa\u0107 IP Slave (<strong>IP Address<\/strong>), czyli w tym przypadku adres IP sterownika Horner RCC.<\/p>\n\n\n\n<p class=\"text-main\">W polu&nbsp;<strong>Timeout Time<\/strong>&nbsp;wybieramy czas odpowiedzi, a w polu&nbsp;<strong>Retry Count<\/strong>&nbsp;ilo\u015b\u0107 pr\u00f3b.<\/p>\n\n\n\n<div class=\"wp-block-image\"><figure class=\"aligncenter\"><img loading=\"lazy\" decoding=\"async\" width=\"682\" height=\"470\" src=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_007.png\" alt=\"\" class=\"wp-image-813\" srcset=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_007.png 682w, https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_007-300x207.png 300w\" sizes=\"auto, (max-width: 682px) 100vw, 682px\" \/><\/figure><\/div>\n\n\n\n<p class=\"text-main\">W przypadku, gdy w zak\u0142adce General zaznaczono Sub-link, nale\u017cy wype\u0142ni\u0107 tylko pole&nbsp;<strong>Retry Count<\/strong>, reszta konfiguracji zostaje przeprowadzana w zak\u0142adce&nbsp;<strong>Sub-link<\/strong>. Przy takiej opcji w zak\u0142adce Sub-link, nale\u017cy wybra\u0107 ilo\u015b\u0107 Slave (<strong>Number of sub-links<\/strong>), a nast\u0119pnie w sekcji&nbsp;<strong>Sub-link<\/strong>&nbsp;trzeba poda\u0107 jego nazw\u0119 (<strong>Name<\/strong>), adres IP (<strong>IP Address<\/strong>) oraz pozosta\u0142e parametry zwi\u0105zane z po\u0142\u0105czeniem.<\/p>\n\n\n\n<div class=\"wp-block-image\"><figure class=\"aligncenter\"><img loading=\"lazy\" decoding=\"async\" width=\"682\" height=\"470\" src=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_008.png\" alt=\"\" class=\"wp-image-814\" srcset=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_008.png 682w, https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_008-300x207.png 300w\" sizes=\"auto, (max-width: 682px) 100vw, 682px\" \/><\/figure><\/div>\n\n\n\n<p class=\"text-main\">Wprowadzone zmiany nale\u017cy zaakceptowa\u0107 wybieraj\u0105c&nbsp;<strong>OK<\/strong>.<\/p>\n\n\n\n<div style=\"height:35px\" aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n\n\n\n<h2 class=\"wp-block-heading\">Tworzenie przyk\u0142adowej aplikacji<\/h2>\n\n\n\n<p class=\"text-main\">W poni\u017cszej aplikacji Astraada HMI b\u0119dzie czyta\u0142a rejestry oraz sterowa\u0142a wyj\u015bciami sterownika Horner.<\/p>\n\n\n\n<p class=\"text-main\">W celu utworzenia aplikacji nale\u017cy skonfigurowa\u0107 sterownik Horner i panel Astraada HMI wed\u0142ug powy\u017cszej instrukcji konfiguracji. Nast\u0119pnie konieczne jest ustalenie odczytywania\/zapisywania obszar\u00f3w pami\u0119ci przez Astraada HMI.<\/p>\n\n\n\n<p class=\"text-main\">W pomocy programu Cscape dost\u0119pna jest tabela przedstawiaj\u0105ca mapowanie rejestr\u00f3w:<\/p>\n\n\n\n<div class=\"wp-block-image\"><figure class=\"aligncenter\"><img loading=\"lazy\" decoding=\"async\" width=\"999\" height=\"641\" src=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_009.png\" alt=\"\" class=\"wp-image-815\" srcset=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_009.png 999w, https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_009-300x192.png 300w, https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_009-768x493.png 768w\" sizes=\"auto, (max-width: 999px) 100vw, 999px\" \/><\/figure><\/div>\n\n\n\n<p class=\"text-main\">Odczytywane b\u0119d\u0105 nast\u0119puj\u0105ce rejestry\/bity: %R102, %SR6, %S5. Zapisywany b\u0119dzie bit %Q1.<br>\nAby to zrobi\u0107 trzeba obliczy\u0107 rejestry zmiennych w Modbus. Rejestr %R102 jest wyj\u015bciem generatora sinusa, %SR6 zawiera czas cyklu programu w cz\u0119\u015bciach dziesi\u0119tnych ms, a %S5 jest wyj\u015bciem generatora sygna\u0142u prostok\u0105tnego o okresie 1s i wype\u0142nieniu 50%.<\/p>\n\n\n\n<p class=\"text-main\">Rejestr Modbus 43001 odpowiada rejestrowi wewn\u0119trznemu %R1, wi\u0119c aby odczyta\u0107 %R102, trzeba do Modbus wpisa\u0107 odpowiednio 43102. Analogicznie, dla wszystkich zmiennych otrzymujemy:<\/p>\n\n\n\n<div class=\"row\">\n<div class=\"col-md-3\"><\/div>\n<div class=\"col-md-6\">\n<div class=\"table-outer\">\n<table class=\"table table-striped\">\n<thead>\n<tr>\n<th style=\"text-align: center;\">RCC<\/th>\n<th style=\"text-align: center;\">Modbus<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td style=\"text-align: center;\">%R102<\/td>\n<td style=\"text-align: center;\">43102<\/td>\n<\/tr>\n<tr>\n<td style=\"text-align: center;\">%SR6<\/td>\n<td style=\"text-align: center;\">34006<\/td>\n<\/tr>\n<tr>\n<td style=\"text-align: center;\">%S5<\/td>\n<td style=\"text-align: center;\">14005R<\/td>\n<\/tr>\n<tr>\n<td style=\"text-align: center;\">%Q1<\/td>\n<td style=\"text-align: center;\">00001<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>&nbsp;<\/p>\n<\/div>\n<\/div>\n<\/div>\n\n\n\n<div style=\"height:20px\" aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n\n\n\n\n\n<div style=\"height:35px\" aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n\n\n\n<h3 class=\"wp-block-heading\">Tworzenie aplikacji w programie <a href=\"https:\/\/www.astor.com.pl\/produkty\/sterowanie\/panele-operatorskie\/astraada-hmi-panel.html\" target=\"_blank\" rel=\"noreferrer noopener\" aria-label=\"ASTRAADA HMI CFG (opens in a new tab)\">ASTRAADA HMI CFG<\/a><\/h3>\n\n\n\n<p class=\"text-main\">Po ustaleniu odczytywanych rejestr\u00f3w i zapisywanych bit\u00f3w, konieczne jest dodanie tag\u00f3w do projektu w programie ASTRAADA HMI CFG poprzez wybranie elementu&nbsp;<strong>Tags<\/strong>&nbsp;z drzewa projektu.<\/p>\n\n\n\n<div class=\"wp-block-image\"><figure class=\"aligncenter\"><img loading=\"lazy\" decoding=\"async\" width=\"288\" height=\"220\" src=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_010.png\" alt=\"\" class=\"wp-image-816\"\/><\/figure><\/div>\n\n\n\n<p class=\"text-main\">Po klikni\u0119ciu w element Tags, wy\u015bwietla si\u0119 okno&nbsp;<strong>Tag Table<\/strong>, gdzie wybieramy \u0142\u0105cze skonfigurowane do komunikacji Modbus (<strong>Modbus TCP Master<\/strong>).<\/p>\n\n\n\n<figure class=\"wp-block-image\"><img loading=\"lazy\" decoding=\"async\" width=\"692\" height=\"375\" src=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_011.png\" alt=\"\" class=\"wp-image-817\" srcset=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_011.png 692w, https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_011-300x163.png 300w\" sizes=\"auto, (max-width: 692px) 100vw, 692px\" \/><\/figure>\n\n\n\n<p class=\"text-main\">W celu dodania tagu nale\u017cy wpisa\u0107 jego nazw\u0119 (<strong>Name<\/strong>) oraz wybra\u0107 typ danych&nbsp;<strong>Data Type<\/strong>.<\/p>\n\n\n\n<div class=\"wp-block-image\"><figure class=\"aligncenter\"><img loading=\"lazy\" decoding=\"async\" width=\"906\" height=\"309\" src=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_012.png\" alt=\"\" class=\"wp-image-818\" srcset=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_012.png 906w, https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_012-300x102.png 300w, https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_012-768x262.png 768w\" sizes=\"auto, (max-width: 906px) 100vw, 906px\" \/><\/figure><\/div>\n\n\n\n<p class=\"text-main\">Klikaj\u0105c w pole&nbsp;<strong>Address<\/strong>&nbsp;a nast\u0119pnie w tr\u00f3jkropek otwiera si\u0119 klawiatura do wpisywania adres\u00f3w:<\/p>\n\n\n\n<div class=\"wp-block-image\"><figure class=\"aligncenter\"><img loading=\"lazy\" decoding=\"async\" width=\"259\" height=\"261\" src=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_013.png\" alt=\"\" class=\"wp-image-819\" srcset=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_013.png 259w, https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_013-150x150.png 150w, https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_013-100x100.png 100w\" sizes=\"auto, (max-width: 259px) 100vw, 259px\" \/><\/figure><\/div>\n\n\n\n<p class=\"text-main\">Wybieramy&nbsp;<strong>Sub-link<\/strong>&nbsp;powi\u0105zany z danym linkiem. Je\u015bli dany link nie posiada sub-link\u00f3w, to pomijamy t\u0105 opcj\u0119. Nast\u0119pnie wpisujemy adres Modbus odpowiedzialny za rejestr&nbsp;<strong>%R102<\/strong>, czyli&nbsp;<strong>43102<\/strong>. Wprowadzone dane akceptujemy przyciskiem&nbsp;<strong>ENT<\/strong>. Pozosta\u0142e zmienne dodajemy analogicznie.<\/p>\n\n\n\n<p class=\"text-main\">Po dodaniu wszystkich tag\u00f3w otrzymujemy tabel\u0119 z 4 pozycjami o nast\u0119puj\u0105cych parametrach:<\/p>\n\n\n\n<div class=\"wp-block-image\"><figure class=\"aligncenter\"><img loading=\"lazy\" decoding=\"async\" width=\"906\" height=\"309\" src=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_014.png\" alt=\"\" class=\"wp-image-820\" srcset=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_014.png 906w, https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_014-300x102.png 300w, https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_014-768x262.png 768w\" sizes=\"auto, (max-width: 906px) 100vw, 906px\" \/><\/figure><\/div>\n\n\n\n<p class=\"text-main\">W ostatnim etapie nale\u017cy doda\u0107 do wizualizacji kontrolki:&nbsp;<strong>Numeric Display<\/strong>,&nbsp;<strong>Toggle Switch<\/strong>oraz&nbsp;<strong>BitLamp<\/strong>&nbsp;i powi\u0105za\u0107 z nimi utworzone tagi.<br>\nPo zapisaniu programu i wgraniu go do sterownika (<strong>Download Data to Panel<\/strong>), nale\u017cy w\u0142\u0105czy\u0107 wizualizacj\u0119 na komputerze przez wybranie zak\u0142adki Tools i opcji&nbsp;<strong>Run online simulation<\/strong>.<\/p>\n\n\n\n<p class=\"text-main\">Zdj\u0119cie poni\u017cej przedstawia wizualizacj\u0119 HMI:<\/p>\n\n\n\n<div class=\"wp-block-image\"><figure class=\"aligncenter\"><img loading=\"lazy\" decoding=\"async\" width=\"388\" height=\"228\" src=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_015.png\" alt=\"\" class=\"wp-image-821\" srcset=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_015.png 388w, https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/AstraadaHorner_TCP_015-300x176.png 300w\" sizes=\"auto, (max-width: 388px) 100vw, 388px\" \/><\/figure><\/div>\n","protected":false},"excerpt":{"rendered":"<p>W celu stworzenia po\u0142\u0105czenia w protokole Modbus TCP konieczna jest konfiguracja urz\u0105dze\u0144 pracuj\u0105cych w tym po\u0142\u0105czeniu. Proces zostanie opisany na przyk\u0142adzie Astraada HMI PANEL AS42TFT1265 (Master) i sterownika Horner RCC1410BC (Slave).<\/p>\n","protected":false},"author":10,"featured_media":805,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[1],"tags":[156,96,110,80,157,41],"class_list":["post-804","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-bez-kategorii","tag-astraada-hmi-cfg","tag-astraada-hmi-panel","tag-cscape","tag-horner-rcc","tag-modbus-tcp","tag-panele-operatorskie"],"acf":[],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v27.3 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\r\n<title>Jak po\u0142\u0105czy\u0107 PLC Horner z panelem Astraada HMI za pomoc\u0105 Modbus?<\/title>\r\n<meta name=\"description\" content=\"W celu stworzenia po\u0142\u0105czenia w protokole Modbus TCP konieczna jest konfiguracja urz\u0105dze\u0144. Proces zostanie opisany na przyk\u0142adzie Astraada HMI i PLC Horner.\" \/>\r\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\r\n<link rel=\"canonical\" href=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\/\" \/>\r\n<meta property=\"og:locale\" content=\"pl_PL\" \/>\r\n<meta property=\"og:type\" content=\"article\" \/>\r\n<meta property=\"og:title\" content=\"Jak po\u0142\u0105czy\u0107 PLC Horner z panelem Astraada HMI za pomoc\u0105 Modbus?\" \/>\r\n<meta property=\"og:description\" content=\"W celu stworzenia po\u0142\u0105czenia w protokole Modbus TCP konieczna jest konfiguracja urz\u0105dze\u0144. Proces zostanie opisany na przyk\u0142adzie Astraada HMI i PLC Horner.\" \/>\r\n<meta property=\"og:url\" content=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\/\" \/>\r\n<meta property=\"og:site_name\" content=\"Poradnik Automatyka\" \/>\r\n<meta property=\"article:published_time\" content=\"2018-09-04T08:04:28+00:00\" \/>\r\n<meta property=\"article:modified_time\" content=\"2020-04-16T13:54:06+00:00\" \/>\r\n<meta property=\"og:image\" content=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/startowe3.png\" \/>\r\n\t<meta property=\"og:image:width\" content=\"891\" \/>\r\n\t<meta property=\"og:image:height\" content=\"372\" \/>\r\n\t<meta property=\"og:image:type\" content=\"image\/png\" \/>\r\n<meta name=\"author\" content=\"Piotr Adamczyk\" \/>\r\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\r\n<meta name=\"twitter:label1\" content=\"Napisane przez\" \/>\n\t<meta name=\"twitter:data1\" content=\"Piotr Adamczyk\" \/>\n\t<meta name=\"twitter:label2\" content=\"Szacowany czas czytania\" \/>\n\t<meta name=\"twitter:data2\" content=\"5 minut\" \/>\r\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\\\/#article\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\\\/\"},\"author\":{\"name\":\"Piotr Adamczyk\",\"@id\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/#\\\/schema\\\/person\\\/11dfcf980fc07f36f7cf4c4561cd0cbe\"},\"headline\":\"Jak po\u0142\u0105czy\u0107 sterownik PLC firmy Horner z panelem operatorskim Astraada HMI za pomoc\u0105 protoko\u0142u Modbus TCP?\",\"datePublished\":\"2018-09-04T08:04:28+00:00\",\"dateModified\":\"2020-04-16T13:54:06+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\\\/\"},\"wordCount\":990,\"commentCount\":0,\"publisher\":{\"@id\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/#organization\"},\"image\":{\"@id\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\\\/#primaryimage\"},\"thumbnailUrl\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/wp-content\\\/uploads\\\/2018\\\/09\\\/startowe3.png\",\"keywords\":[\"Astraada HMI CFG\",\"Astraada HMI Panel\",\"Cscape\",\"Horner RCC\",\"Modbus TCP\",\"Panele operatorskie\"],\"inLanguage\":\"pl-PL\",\"potentialAction\":[{\"@type\":\"CommentAction\",\"name\":\"Comment\",\"target\":[\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\\\/#respond\"]}]},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\\\/\",\"url\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\\\/\",\"name\":\"Jak po\u0142\u0105czy\u0107 PLC Horner z panelem Astraada HMI za pomoc\u0105 Modbus?\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/#website\"},\"primaryImageOfPage\":{\"@id\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\\\/#primaryimage\"},\"image\":{\"@id\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\\\/#primaryimage\"},\"thumbnailUrl\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/wp-content\\\/uploads\\\/2018\\\/09\\\/startowe3.png\",\"datePublished\":\"2018-09-04T08:04:28+00:00\",\"dateModified\":\"2020-04-16T13:54:06+00:00\",\"description\":\"W celu stworzenia po\u0142\u0105czenia w protokole Modbus TCP konieczna jest konfiguracja urz\u0105dze\u0144. Proces zostanie opisany na przyk\u0142adzie Astraada HMI i PLC Horner.\",\"breadcrumb\":{\"@id\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\\\/#breadcrumb\"},\"inLanguage\":\"pl-PL\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\\\/\"]}]},{\"@type\":\"ImageObject\",\"inLanguage\":\"pl-PL\",\"@id\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\\\/#primaryimage\",\"url\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/wp-content\\\/uploads\\\/2018\\\/09\\\/startowe3.png\",\"contentUrl\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/wp-content\\\/uploads\\\/2018\\\/09\\\/startowe3.png\",\"width\":891,\"height\":372},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\\\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Bez kategorii\",\"item\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/category\\\/bez-kategorii\\\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"Jak po\u0142\u0105czy\u0107 sterownik PLC firmy Horner z panelem operatorskim Astraada HMI za pomoc\u0105 protoko\u0142u Modbus TCP?\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/#website\",\"url\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/\",\"name\":\"Poradnik Automatyka\",\"description\":\"Poradnik Automatyka to przydatne kursy, u\u017cyteczne artyku\u0142y i merytoryczne webinary dla ka\u017cdego automatyka i elektryka.\",\"publisher\":{\"@id\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/#organization\"},\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"pl-PL\"},{\"@type\":\"Organization\",\"@id\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/#organization\",\"name\":\"ASTOR\",\"url\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/\",\"logo\":{\"@type\":\"ImageObject\",\"inLanguage\":\"pl-PL\",\"@id\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/#\\\/schema\\\/logo\\\/image\\\/\",\"url\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/wp-content\\\/uploads\\\/2018\\\/08\\\/ASTOR_zwykly_sam_logotyp.png\",\"contentUrl\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/wp-content\\\/uploads\\\/2018\\\/08\\\/ASTOR_zwykly_sam_logotyp.png\",\"width\":3322,\"height\":1078,\"caption\":\"ASTOR\"},\"image\":{\"@id\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/#\\\/schema\\\/logo\\\/image\\\/\"}},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/#\\\/schema\\\/person\\\/11dfcf980fc07f36f7cf4c4561cd0cbe\",\"name\":\"Piotr Adamczyk\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"pl-PL\",\"@id\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/wp-content\\\/uploads\\\/2023\\\/04\\\/P.-Adamczyk.jpg\",\"url\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/wp-content\\\/uploads\\\/2023\\\/04\\\/P.-Adamczyk.jpg\",\"contentUrl\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/wp-content\\\/uploads\\\/2023\\\/04\\\/P.-Adamczyk.jpg\",\"caption\":\"Piotr Adamczyk\"},\"description\":\"Dyrektor Dzia\u0142u Rozwoju Sprzeda\u017cy w centrali ASTOR. Od 15 lat zajmuje si\u0119 szeroko poj\u0119tymi zagadnieniami zwi\u0105zanymi z systemami sterowania, wizualizacj\u0105 HMI oraz komunikacj\u0105 bezprzewodow\u0105 GSM. Manager produkt\u00f3w z oferty Emerson Machine Automation Solution oraz urz\u0105dze\u0144 zintegrowanych Horner APG. Specjalista w zakresie system\u00f3w wysokiej dost\u0119pno\u015bci. Absolwent Politechniki Rzeszowskiej, Wydzia\u0142u Elektrotechniki i Informatyki (kierunek Informatyka, specjalno\u015b\u0107 systemy i sieci komputerowe).\",\"sameAs\":[\"https:\\\/\\\/pl.linkedin.com\\\/in\\\/piotr-adamczyk-379b7646\\\/countrypl+languagepl?trk=people-guest_people_search-card\"],\"url\":\"https:\\\/\\\/www.astor.com.pl\\\/poradnikautomatyka\\\/autor\\\/piotra\\\/\"}]}<\/script>\r\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"Jak po\u0142\u0105czy\u0107 PLC Horner z panelem Astraada HMI za pomoc\u0105 Modbus?","description":"W celu stworzenia po\u0142\u0105czenia w protokole Modbus TCP konieczna jest konfiguracja urz\u0105dze\u0144. Proces zostanie opisany na przyk\u0142adzie Astraada HMI i PLC Horner.","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\/","og_locale":"pl_PL","og_type":"article","og_title":"Jak po\u0142\u0105czy\u0107 PLC Horner z panelem Astraada HMI za pomoc\u0105 Modbus?","og_description":"W celu stworzenia po\u0142\u0105czenia w protokole Modbus TCP konieczna jest konfiguracja urz\u0105dze\u0144. Proces zostanie opisany na przyk\u0142adzie Astraada HMI i PLC Horner.","og_url":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\/","og_site_name":"Poradnik Automatyka","article_published_time":"2018-09-04T08:04:28+00:00","article_modified_time":"2020-04-16T13:54:06+00:00","og_image":[{"width":891,"height":372,"url":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/startowe3.png","type":"image\/png"}],"author":"Piotr Adamczyk","twitter_card":"summary_large_image","twitter_misc":{"Napisane przez":"Piotr Adamczyk","Szacowany czas czytania":"5 minut"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\/#article","isPartOf":{"@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\/"},"author":{"name":"Piotr Adamczyk","@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/#\/schema\/person\/11dfcf980fc07f36f7cf4c4561cd0cbe"},"headline":"Jak po\u0142\u0105czy\u0107 sterownik PLC firmy Horner z panelem operatorskim Astraada HMI za pomoc\u0105 protoko\u0142u Modbus TCP?","datePublished":"2018-09-04T08:04:28+00:00","dateModified":"2020-04-16T13:54:06+00:00","mainEntityOfPage":{"@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\/"},"wordCount":990,"commentCount":0,"publisher":{"@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/#organization"},"image":{"@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\/#primaryimage"},"thumbnailUrl":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/startowe3.png","keywords":["Astraada HMI CFG","Astraada HMI Panel","Cscape","Horner RCC","Modbus TCP","Panele operatorskie"],"inLanguage":"pl-PL","potentialAction":[{"@type":"CommentAction","name":"Comment","target":["https:\/\/www.astor.com.pl\/poradnikautomatyka\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\/#respond"]}]},{"@type":"WebPage","@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\/","url":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\/","name":"Jak po\u0142\u0105czy\u0107 PLC Horner z panelem Astraada HMI za pomoc\u0105 Modbus?","isPartOf":{"@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/#website"},"primaryImageOfPage":{"@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\/#primaryimage"},"image":{"@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\/#primaryimage"},"thumbnailUrl":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/startowe3.png","datePublished":"2018-09-04T08:04:28+00:00","dateModified":"2020-04-16T13:54:06+00:00","description":"W celu stworzenia po\u0142\u0105czenia w protokole Modbus TCP konieczna jest konfiguracja urz\u0105dze\u0144. Proces zostanie opisany na przyk\u0142adzie Astraada HMI i PLC Horner.","breadcrumb":{"@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\/#breadcrumb"},"inLanguage":"pl-PL","potentialAction":[{"@type":"ReadAction","target":["https:\/\/www.astor.com.pl\/poradnikautomatyka\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\/"]}]},{"@type":"ImageObject","inLanguage":"pl-PL","@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\/#primaryimage","url":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/startowe3.png","contentUrl":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/09\/startowe3.png","width":891,"height":372},{"@type":"BreadcrumbList","@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/jak-polaczyc-sterownik-plc-firmy-horner-z-panelem-operatorskim-astraada-hmi-za-pomoca-protokolu-modbus-tcp\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Bez kategorii","item":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/category\/bez-kategorii\/"},{"@type":"ListItem","position":2,"name":"Jak po\u0142\u0105czy\u0107 sterownik PLC firmy Horner z panelem operatorskim Astraada HMI za pomoc\u0105 protoko\u0142u Modbus TCP?"}]},{"@type":"WebSite","@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/#website","url":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/","name":"Poradnik Automatyka","description":"Poradnik Automatyka to przydatne kursy, u\u017cyteczne artyku\u0142y i merytoryczne webinary dla ka\u017cdego automatyka i elektryka.","publisher":{"@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/#organization"},"potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"pl-PL"},{"@type":"Organization","@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/#organization","name":"ASTOR","url":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/","logo":{"@type":"ImageObject","inLanguage":"pl-PL","@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/#\/schema\/logo\/image\/","url":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/08\/ASTOR_zwykly_sam_logotyp.png","contentUrl":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/08\/ASTOR_zwykly_sam_logotyp.png","width":3322,"height":1078,"caption":"ASTOR"},"image":{"@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/#\/schema\/logo\/image\/"}},{"@type":"Person","@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/#\/schema\/person\/11dfcf980fc07f36f7cf4c4561cd0cbe","name":"Piotr Adamczyk","image":{"@type":"ImageObject","inLanguage":"pl-PL","@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/04\/P.-Adamczyk.jpg","url":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/04\/P.-Adamczyk.jpg","contentUrl":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/04\/P.-Adamczyk.jpg","caption":"Piotr Adamczyk"},"description":"Dyrektor Dzia\u0142u Rozwoju Sprzeda\u017cy w centrali ASTOR. Od 15 lat zajmuje si\u0119 szeroko poj\u0119tymi zagadnieniami zwi\u0105zanymi z systemami sterowania, wizualizacj\u0105 HMI oraz komunikacj\u0105 bezprzewodow\u0105 GSM. Manager produkt\u00f3w z oferty Emerson Machine Automation Solution oraz urz\u0105dze\u0144 zintegrowanych Horner APG. Specjalista w zakresie system\u00f3w wysokiej dost\u0119pno\u015bci. Absolwent Politechniki Rzeszowskiej, Wydzia\u0142u Elektrotechniki i Informatyki (kierunek Informatyka, specjalno\u015b\u0107 systemy i sieci komputerowe).","sameAs":["https:\/\/pl.linkedin.com\/in\/piotr-adamczyk-379b7646\/countrypl+languagepl?trk=people-guest_people_search-card"],"url":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/autor\/piotra\/"}]}},"_links":{"self":[{"href":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-json\/wp\/v2\/posts\/804","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-json\/wp\/v2\/users\/10"}],"replies":[{"embeddable":true,"href":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-json\/wp\/v2\/comments?post=804"}],"version-history":[{"count":0,"href":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-json\/wp\/v2\/posts\/804\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-json\/wp\/v2\/media\/805"}],"wp:attachment":[{"href":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-json\/wp\/v2\/media?parent=804"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-json\/wp\/v2\/categories?post=804"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-json\/wp\/v2\/tags?post=804"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}