{"id":15555,"date":"2023-02-06T18:14:43","date_gmt":"2023-02-06T17:14:43","guid":{"rendered":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/?p=15555"},"modified":"2023-05-15T19:51:36","modified_gmt":"2023-05-15T17:51:36","slug":"komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax","status":"publish","type":"post","link":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/","title":{"rendered":"Komunikacja paneli Astraada HMI ze sterownikami Emerson serii VersaMax"},"content":{"rendered":"\n<div style=\"height:30px\" aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n\n\n\n<div class=\"dowiesz-sie\">\n<h3>Z tego artyku\u0142u dowiesz si\u0119:<\/h3>\n<ul class=\"bulleted\">\n<li>jak skonfigurowa\u0107 po\u0142\u0105czenie panelu Astraada HMI ze sterownikiem Emerson VersaMax,<\/li>\n<li>jak skonfigurowa\u0107 sterownik VersaMax do wymiany informacji za po\u015brednictwem port\u00f3w Ethernet oraz RS-232,<\/li>\n<li>jak powinna wygl\u0105da\u0107 prawid\u0142owa konfiguracja po stronie panelu Astraada HMI.<\/li>\n<\/ul>\n<\/div>\n\n\n\n<div style=\"height:30px\" aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n\n\n\n<p>W tym artykule opisujemy krok po kroku, jak skonfigurowa\u0107 po\u0142\u0105czenie <a href=\"https:\/\/www.astor.com.pl\/sklep\/sterowanie\/panele-operatorskie\/astraada-hmi-panel\/astraada-hmi-panel-standard.html\" target=\"_blank\" rel=\"noreferrer noopener\">panelu Astraada HMI z serii AS46<\/a> ze sterownikami <a href=\"https:\/\/www.astor.com.pl\/sklep\/sterowanie\/sterowniki-plc\/versamax.html\" target=\"_blank\" rel=\"noreferrer noopener\">Emerson VersaMax<\/a>, z wykorzystaniem portu Ethernet oraz portu szeregowego RS-232.<\/p>\n\n\n\n<p>Komunikacj\u0119 paneli Astraada HMI ze sterownikami VersaMax umo\u017cliwia driver komunikacyjny wbudowany w oprogramowanie narz\u0119dziowe&nbsp;<a href=\"https:\/\/www.astor.com.pl\/wsparcie\/dokumentacja-techniczna\/id\/26133\">Astraada HMI CFG<\/a>. W celu uruchomienia komunikacji konieczna jest odpowiednia konfiguracja drivera po stronie panelu i sterownika. W niniejszym artykule poka\u017cemy, jak to zrobi\u0107.<\/p>\n\n\n\n<p>Warto doda\u0107, \u017ce dzi\u0119ki komunikacji z panelami Astraada HMI przy odpowiednich ustawieniach mo\u017cemy skorzysta\u0107 z opcji zdalnego programowania sterownik\u00f3w, dzi\u0119ki us\u0142udze IDCS. <\/p>\n\n\n\n<p><\/p>\n\n\n\n<div class=\"link-box d-flex align-items-center\">\r\n\t\t\t\t\t\t\t<img decoding=\"async\" src=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/themes\/poradnik\/public\/images\/icons\/icon-link.svg\" alt=\"arrow\" class=\"ml-3\">\r\n\t\t\t\t\t\t\t<\/a>\r\n\t\t\t\t\t\t\t<div><p>Wi\u0119cej na ten temat przeczytasz w artykule<br \/>\n<strong><a href=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/astraada-hmi-w-chmurze-zdalny-dostep-do-paneli-operatorskich\/\">Astraada HMI w chmurze. Zdalny dost\u0119p do paneli operatorskich<\/a><\/strong>.<\/p>\n<\/div>\r\n\t\t\t\t\t<\/div>\r\n\t\n\n\n\n<div style=\"height:20px\" aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n\n\n\n<h2 class=\"wp-block-heading\">Komunikacja z u\u017cyciem sieci Ethernet<\/h2>\n\n\n\n<h3 class=\"wp-block-heading\">Konfiguracja sterownika<\/h3>\n\n\n\n<p>Po podstawowej konfiguracji sterownika w oprogramowaniu <strong><em>Proficy Machine Edition <\/em><\/strong>nale\u017cy rozwin\u0105\u0107 drzewo projektu przy polu <strong><em>Target1<\/em><\/strong>. Nast\u0119pnie w zak\u0142adce <strong><em>Main Rack<\/em><\/strong> klikamy dwukrotnie na <strong><em>Slot 0<\/em><\/strong> oznaczaj\u0105cy jednostk\u0119 centraln\u0105. W oknie jej konfiguracji przechodzimy do zak\u0142adki <strong><em>Ethernet<\/em><\/strong> i w polu <strong><em>IP Adress<\/em><\/strong> wpisujemy adres sterownika.<\/p>\n\n\n\n<div style=\"height:20px\" aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n\n\n<div class=\"wp-block-image\">\n<figure class=\"aligncenter size-large\"><img loading=\"lazy\" decoding=\"async\" width=\"840\" height=\"204\" src=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image1-1-840x204.jpg\" alt=\"\" class=\"wp-image-15560\" srcset=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image1-1-840x204.jpg 840w, https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image1-1-768x186.jpg 768w, https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image1-1.jpg 1131w\" sizes=\"auto, (max-width: 840px) 100vw, 840px\" \/><\/figure>\n<\/div>\n\n\n<div style=\"height:20px\" aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n\n\n\n<p>Po wykonaniu tych czynno\u015bci, skompilowaniu programu i pobraniu aplikacji na sterownik, mo\u017cliwa b\u0119dzie komunikacja z panelem HMI od strony sterownika.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\">Konfiguracja po\u0142\u0105czenia na panelu HMI<\/h3>\n\n\n\n<p>W trakcie tworzenia projektu na panel HMI w oprogramowaniu <strong><em>Astraada HMI CFG<\/em><\/strong> nale\u017cy skonfigurowa\u0107 odpowiedni link komunikacyjny dla sterownika VersaMax. Je\u017celi nie zrobiono tego na etapie tworzenia nowego projektu, mo\u017cna doda\u0107 nowy link, klikaj\u0105c prawym przyciskiem myszy na obiekt <strong><em>&nbsp;Links <\/em><\/strong>w drzewie projektu i wybra\u0107 opcj\u0119 <strong><em>Add link\u2026<\/em><\/strong><\/p>\n\n\n\n<div style=\"height:20px\" aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n\n\n<div class=\"wp-block-image\">\n<figure class=\"aligncenter size-large\"><img loading=\"lazy\" decoding=\"async\" width=\"294\" height=\"360\" src=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image2-1.jpg\" alt=\"\" class=\"wp-image-15561\"\/><\/figure>\n<\/div>\n\n\n<div style=\"height:20px\" aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n\n\n\n<p>W zak\u0142adce <strong><em>General <\/em><\/strong>nale\u017cy wybra\u0107 typ linku <strong><em>Direct Link (Ethernet)<\/em><\/strong>, a w polach <strong><em>Device\/Server <\/em><\/strong>wybra\u0107 kolejno <strong><em>GE Corporation <\/em><\/strong>oraz <strong><em>SRTP Ethernet (Micro)<\/em><\/strong>. Je\u017celi chcemy mie\u0107 mo\u017cliwo\u015b\u0107 programowania sterownika przez panel operatorski za pomoc\u0105 us\u0142ugi IDCS, zaznaczamy opcj\u0119 <strong><em>Allow to be used by remote links through IDCS<\/em><\/strong>.<\/p>\n\n\n\n<div style=\"height:20px\" aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n\n\n<div class=\"wp-block-image\">\n<figure class=\"aligncenter size-large\"><img loading=\"lazy\" decoding=\"async\" width=\"800\" height=\"576\" src=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image3-1.jpg\" alt=\"\" class=\"wp-image-15562\" srcset=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image3-1.jpg 800w, https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image3-1-768x553.jpg 768w\" sizes=\"auto, (max-width: 800px) 100vw, 800px\" \/><\/figure>\n<\/div>\n\n\n<div style=\"height:20px\" aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n\n\n\n<p>Nast\u0119pnie w zak\u0142adce <strong><em>Parameter<\/em><\/strong> w polu <strong><em>IP Adress<\/em><\/strong> wpisujemy adres sterownika, z kt\u00f3rym chcemy si\u0119 komunikowa\u0107 (sterownik i panel musz\u0105 znajdowa\u0107 si\u0119 w tej samej podsieci). Zaznaczamy r\u00f3wnie\u017c opcj\u0119 <strong><em>Use Default Port<\/em><\/strong>. Ustawiamy tak\u017ce <strong><em>Timeout Time<\/em><\/strong> na r\u00f3\u017cny od zera.<\/p>\n\n\n\n<div style=\"height:20px\" aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n\n\n<div class=\"wp-block-image\">\n<figure class=\"aligncenter size-large\"><img loading=\"lazy\" decoding=\"async\" width=\"799\" height=\"570\" src=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image4-1.jpg\" alt=\"\" class=\"wp-image-15563\" srcset=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image4-1.jpg 799w, https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image4-1-768x548.jpg 768w\" sizes=\"auto, (max-width: 799px) 100vw, 799px\" \/><\/figure>\n<\/div>\n\n\n<div style=\"height:20px\" aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n\n\n\n<p>Zmiany zatwierdzamy przyciskiem <strong><em>OK<\/em><\/strong>. Komunikacja mi\u0119dzy sterownikiem i panelem jest ju\u017c prawid\u0142owo skonfigurowana. Mo\u017cemy teraz odczytywa\u0107 i przypisywa\u0107 warto\u015bci zmiennych z pami\u0119ci wewn\u0119trznej sterownika.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Komunikacja z u\u017cyciem portu szeregowego<\/h2>\n\n\n\n<h3 class=\"wp-block-heading\">Konfiguracja sterownika<\/h3>\n\n\n\n<p>Po podstawowej konfiguracji sterownika w oprogramowaniu <strong><em>Proficy Machine Edition <\/em><\/strong>nale\u017cy rozwin\u0105\u0107 drzewo projektu przy polu<strong><em> Target1<\/em><\/strong>. Nast\u0119pnie w zak\u0142adce <strong><em>Main Rack<\/em><\/strong> klikamy dwukrotnie na <strong><em>Slot 0<\/em><\/strong> oznaczaj\u0105cy jednostk\u0119 centraln\u0105. W oknie jej konfiguracji wybieramy port, kt\u00f3ry zamierzamy u\u017cywa\u0107 do komunikacji. W tym poradniku zostanie u\u017cyty <strong><em>Port 1 (RS-232)<\/em><\/strong>. Nast\u0119pnie ustawiamy tryb pracy portu na SNP. Dalszymi krokami jest konfiguracja parametr\u00f3w portu oraz ID Sterownika, czyli uzupe\u0142nienie poni\u017cszych p\u00f3l, w tym<strong><em> SNP ID<\/em><\/strong>.<\/p>\n\n\n\n<div style=\"height:20px\" aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n\n\n<div class=\"wp-block-image\">\n<figure class=\"aligncenter size-large\"><img loading=\"lazy\" decoding=\"async\" width=\"840\" height=\"208\" src=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image5-840x208.jpg\" alt=\"\" class=\"wp-image-15564\" srcset=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image5-840x208.jpg 840w, https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image5-768x190.jpg 768w, https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image5.jpg 1119w\" sizes=\"auto, (max-width: 840px) 100vw, 840px\" \/><\/figure>\n<\/div>\n\n\n<div style=\"height:20px\" aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n\n\n\n<p>Program jest gotowy do wgrania na sterownik.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\">Konfiguracja panelu HMI<\/h3>\n\n\n\n<p>W trakcie tworzenia projektu na panel HMI w oprogramowaniu <strong><em>Astraada HMI CFG<\/em><\/strong> nale\u017cy skonfigurowa\u0107 dla sterownika VersaMax odpowiedni link komunikacyjny. Je\u017celi nie zrobiono tego na etapie tworzenia nowego projektu, mo\u017cna doda\u0107 nowy link klikaj\u0105c prawym przyciskiem myszy na obiekt<strong><em> Links <\/em><\/strong>w drzewie projektu i wybra\u0107 opcj\u0119 <strong><em>Add link\u2026<\/em><\/strong><\/p>\n\n\n\n<div style=\"height:20px\" aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n\n\n<div class=\"wp-block-image\">\n<figure class=\"aligncenter size-large\"><img loading=\"lazy\" decoding=\"async\" width=\"294\" height=\"360\" src=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image2-1.jpg\" alt=\"\" class=\"wp-image-15561\"\/><\/figure>\n<\/div>\n\n\n<div style=\"height:20px\" aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n\n\n\n<p>W zak\u0142adce <strong><em>General <\/em><\/strong>nale\u017cy wybra\u0107 typ linku <strong><em>Direct Link (COM) <\/em><\/strong>a w polach <strong><em>Device\/Server <\/em><\/strong>wybra\u0107 kolejno <strong><em>GE Corporation <\/em><\/strong>oraz <strong><em>VersaMax Series (SNP)<\/em><\/strong>. Je\u017celi chcemy mie\u0107 mo\u017cliwo\u015b\u0107 programowania sterownika przez panel operatorski za pomoc\u0105 us\u0142ugi IDCS to zaznaczamy checkbox <strong><em>Allow to be used by remote links through IDCS<\/em><\/strong>. Ostatnim krokiem jest wyb\u00f3r portu z panelu HMI, po kt\u00f3rym b\u0119dzie odbywa\u0142a si\u0119 komunikacja.<\/p>\n\n\n\n<div style=\"height:20px\" aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n\n\n<div class=\"wp-block-image\">\n<figure class=\"aligncenter size-large\"><img loading=\"lazy\" decoding=\"async\" width=\"800\" height=\"568\" src=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image6.jpg\" alt=\"\" class=\"wp-image-15565\" srcset=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image6.jpg 800w, https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image6-768x545.jpg 768w\" sizes=\"auto, (max-width: 800px) 100vw, 800px\" \/><\/figure>\n<\/div>\n\n\n<div style=\"height:20px\" aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n\n\n\n<p>Nast\u0119pnie w zak\u0142adce <strong><em>Parameter<\/em><\/strong> w polu <strong><em>PLC Adress<\/em><\/strong> wpisujemy adres ID sterownika, kt\u00f3ry ustalili\u015bmy podczas jego konfiguracji. Zaznaczamy r\u00f3wnie\u017c opcj\u0119 <strong><em>Use Default Port<\/em><\/strong>. Ustawiamy tak\u017ce <strong><em>Timeout Time<\/em><\/strong> na r\u00f3\u017cny od zera. Ustawiamy r\u00f3wnie\u017c parametry z\u0142\u0105cza szeregowego, czyli parzysto\u015b\u0107, pr\u0119dko\u015b\u0107 oraz ilo\u015b\u0107 bit\u00f3w danych w zak\u0142adce <strong><em>Transmission<\/em><\/strong>. Wszystkie dane powinny by\u0107 takie same jak te podane podczas konfiguracji sterownika.<\/p>\n\n\n\n<div style=\"height:20px\" aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n\n\n<div class=\"wp-block-image\">\n<figure class=\"aligncenter size-large\"><img loading=\"lazy\" decoding=\"async\" width=\"800\" height=\"579\" src=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image7.jpg\" alt=\"\" class=\"wp-image-15566\" srcset=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image7.jpg 800w, https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image7-768x556.jpg 768w\" sizes=\"auto, (max-width: 800px) 100vw, 800px\" \/><\/figure>\n<\/div>\n\n\n<div style=\"height:20px\" aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n\n\n\n<p>Ustawiamy r\u00f3wnie\u017c <strong><em>Timeout Time<\/em><\/strong> na r\u00f3\u017cny od zera. Zmiany zatwierdzamy przyciskiem <strong><em>OK<\/em><\/strong>. Komunikacja mi\u0119dzy sterownikiem i panelem jest ju\u017c prawid\u0142owo skonfigurowana. Mo\u017cemy teraz odczytywa\u0107 i przypisywa\u0107 warto\u015bci zmiennych z pami\u0119ci wewn\u0119trznej sterownika u\u017cywaj\u0105c portu szeregowego.<\/p>\n\n\n\n<div style=\"height:50px\" aria-hidden=\"true\" class=\"wp-block-spacer\"><\/div>\n\n\n\n<p><\/p>\n\n\n\n            <div id=\"mailerlite-form_9\" data-temp-id=\"69da9fcedde70\">\n                <div class=\"mailerlite-form\">\n                    <form action=\"\" method=\"post\" novalidate>\n                                                    <div class=\"mailerlite-form-title\"><h3>Newsletter Poradnika Automatyka<\/h3><\/div>\n                                                <div class=\"mailerlite-form-description\"><p>Czytaj trendy i inspiracje, podstawy automatyki, automatyk\u0119 w praktyce<\/p>\n<\/div>\n                        <div class=\"mailerlite-form-inputs\">\n                                                                                            <div class=\"mailerlite-form-field\">\n                                    <label for=\"mailerlite-9-field-email\">Email<\/label>\n                                    <input id=\"mailerlite-9-field-email\"\n                                           type=\"email\" required=\"required\"                                            name=\"form_fields[email]\"\n                                           placeholder=\"Email\"\/>\n                                <\/div>\n                                                        <div class=\"mailerlite-form-loader\">Please wait...<\/div>\n                            <div class=\"mailerlite-subscribe-button-container\">\n                                <button class=\"mailerlite-subscribe-submit\" type=\"submit\">\n                                    Zapisz si\u0119                                <\/button>\n                            <\/div>\n                            <input type=\"hidden\" name=\"form_id\" value=\"9\"\/>\n                            <input type=\"hidden\" name=\"action\" value=\"mailerlite_subscribe_form\"\/>\n                            <input type=\"hidden\" name=\"ml_nonce\" value=\"771fd51215\"\/>\n                        <\/div>\n                        <div class=\"mailerlite-form-response\">\n                                                            <h4><p>Dzi\u0119kujemy za zapis do newslettera!<\/p>\n<\/h4>\n                                                    <\/div>\n                    <\/form>\n                <\/div>\n            <\/div>\n        <script type=\"text\/javascript\" src='https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/plugins\/official-mailerlite-sign-up-forms\/assets\/js\/localization\/validation-messages.js'><\/script>\n         <script type=\"text\/javascript\"> var selectedLanguage = \"pl\"; var validationMessages = messages[\"en\"]; if(selectedLanguage) { validationMessages = messages[selectedLanguage]; } window.addEventListener(\"load\", function () { var form_container = document.querySelector(`#mailerlite-form_9[data-temp-id=\"69da9fcedde70\"] form`); let submitButton = form_container.querySelector('.mailerlite-subscribe-submit'); submitButton.disabled = true; fetch('https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-admin\/admin-ajax.php', { method: 'POST', headers:{ 'Content-Type': 'application\/x-www-form-urlencoded', }, body: new URLSearchParams({ \"action\" : \"ml_create_nonce\", \"ml_nonce\" : form_container.querySelector(\"input[name='ml_nonce']\").value }) }) .then((response) => response.json()) .then((json) => { if(json.success) { form_container.querySelector(\"input[name='ml_nonce']\").value = json.data.ml_nonce; submitButton.disabled = false; } }) .catch((error) => { console.error('Error:', error); }); form_container.addEventListener('submit', (e) => { e.preventDefault(); let data = new URLSearchParams(new FormData(form_container)).toString(); let validationError = false; document.querySelectorAll('.mailerlite-form-error').forEach(el => el.remove()); Array.from(form_container.elements).forEach((input) => { if(input.type !== 'hidden') { if(input.required) { if(input.value == '') { validationError = true; let error = document.createElement(\"span\"); error.className = 'mailerlite-form-error'; error.textContent = validationMessages.required; input.after(error); return false; } } if((input.type == \"email\") && (!validateEmail(input.value))) { validationError = true; let error = document.createElement(\"span\"); error.className = 'mailerlite-form-error'; error.textContent = validationMessages.email; input.after(error); return false; } } }); if(validationError) { return false; } fade.out(form_container.querySelector('.mailerlite-subscribe-button-container'), () => { fade.in(form_container.querySelector('.mailerlite-form-loader')); }); fetch('https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-admin\/admin-ajax.php', { method: 'POST', headers:{ 'Content-Type': 'application\/x-www-form-urlencoded', }, body: data }) .then((response) => { fade.out(form_container.querySelector('.mailerlite-form-inputs'), () => { fade.in(form_container.querySelector('.mailerlite-form-response')); }); }) .catch((error) => { console.error('Error:', error); }); }); }, false); var fade = { out: function(el, fn = false) { var fadeOutEffect = setInterval(function () { if (!el.style.opacity) { el.style.opacity = 1; } if (el.style.opacity > 0) { el.style.opacity -= 0.1; } else { el.style.display = 'none'; clearInterval(fadeOutEffect); } }, 50); if( typeof (fn) == 'function') { fn(); } }, in: function(el) { var fadeInEffect = setInterval(function () { if (!el.style.opacity) { el.style.opacity = 0; } if (el.style.opacity < 1) { el.style.opacity = Number(el.style.opacity) + 0.1; } else { el.style.display = 'block'; clearInterval(fadeInEffect); } }, 50); } }; function validateEmail(email){ if(email.match( \/^(([^<>()[\\]\\\\.,;:\\s@\\\"]+(\\.[^<>()[\\]\\\\.,;:\\s@\\\"]+)*)|(\\\".+\\\"))@((\\[[0-9]{1,3}\\.[0-9]{1,3}\\.[0-9]{1,3}\\.[0-9]{1,3}\\])|(([a-zA-Z\\-0-9]+\\.)+[a-zA-Z]{2,}))$\/ )) { return true; } return false; } <\/script> \n","protected":false},"excerpt":{"rendered":"<p>W tym artykule opisujemy krok po kroku, jak skonfigurowa\u0107 po\u0142\u0105czenie panelu Astraada HMI z serii AS46 ze sterownikami Emerson VersaMax, z wykorzystaniem portu Ethernet oraz portu szeregowego RS-232.<\/p>\n","protected":false},"author":50,"featured_media":15560,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[233],"tags":[96,86],"class_list":["post-15555","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-dla-uzytkownikow-produktow-astor","tag-astraada-hmi-panel","tag-versamax"],"acf":[],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v26.7 - https:\/\/yoast.com\/wordpress\/plugins\/seo\/ -->\r\n<title>Komunikacja paneli Astraada HMI ze sterownikami Emerson serii VersaMax | Poradnik Automatyka<\/title>\r\n<meta name=\"description\" content=\"Konfigurujemy po\u0142\u0105czenie panelu Astraada HMI ze sterownikami Emerson VersaMax, z wykorzystaniem portu Ethernet oraz portu szeregowego RS-232.\" \/>\r\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\r\n<link rel=\"canonical\" href=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/\" \/>\r\n<meta property=\"og:locale\" content=\"pl_PL\" \/>\r\n<meta property=\"og:type\" content=\"article\" \/>\r\n<meta property=\"og:title\" content=\"Komunikacja paneli Astraada HMI ze sterownikami Emerson serii VersaMax | Poradnik Automatyka\" \/>\r\n<meta property=\"og:description\" content=\"Konfigurujemy po\u0142\u0105czenie panelu Astraada HMI ze sterownikami Emerson VersaMax, z wykorzystaniem portu Ethernet oraz portu szeregowego RS-232.\" \/>\r\n<meta property=\"og:url\" content=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/\" \/>\r\n<meta property=\"og:site_name\" content=\"Poradnik Automatyka\" \/>\r\n<meta property=\"article:published_time\" content=\"2023-02-06T17:14:43+00:00\" \/>\r\n<meta property=\"article:modified_time\" content=\"2023-05-15T17:51:36+00:00\" \/>\r\n<meta property=\"og:image\" content=\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image1-1.jpg\" \/>\r\n\t<meta property=\"og:image:width\" content=\"1131\" \/>\r\n\t<meta property=\"og:image:height\" content=\"274\" \/>\r\n\t<meta property=\"og:image:type\" content=\"image\/jpeg\" \/>\r\n<meta name=\"author\" content=\"Mateusz Fas\" \/>\r\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\r\n<meta name=\"twitter:label1\" content=\"Napisane przez\" \/>\n\t<meta name=\"twitter:data1\" content=\"Mateusz Fas\" \/>\n\t<meta name=\"twitter:label2\" content=\"Szacowany czas czytania\" \/>\n\t<meta name=\"twitter:data2\" content=\"6 minut\" \/>\r\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\/\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/#article\",\"isPartOf\":{\"@id\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/\"},\"author\":{\"name\":\"Mateusz Fas\",\"@id\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/#\/schema\/person\/7029e2ba4cc4e4e1c9bfd3b6a47a8b67\"},\"headline\":\"Komunikacja paneli Astraada HMI ze sterownikami Emerson serii VersaMax\",\"datePublished\":\"2023-02-06T17:14:43+00:00\",\"dateModified\":\"2023-05-15T17:51:36+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/\"},\"wordCount\":761,\"commentCount\":0,\"publisher\":{\"@id\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/#organization\"},\"image\":{\"@id\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/#primaryimage\"},\"thumbnailUrl\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image1-1.jpg\",\"keywords\":[\"Astraada HMI Panel\",\"VersaMax\"],\"articleSection\":[\"Produkty ASTOR\"],\"inLanguage\":\"pl-PL\",\"potentialAction\":[{\"@type\":\"CommentAction\",\"name\":\"Comment\",\"target\":[\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/#respond\"]}]},{\"@type\":\"WebPage\",\"@id\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/\",\"url\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/\",\"name\":\"Komunikacja paneli Astraada HMI ze sterownikami Emerson serii VersaMax | Poradnik Automatyka\",\"isPartOf\":{\"@id\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/#website\"},\"primaryImageOfPage\":{\"@id\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/#primaryimage\"},\"image\":{\"@id\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/#primaryimage\"},\"thumbnailUrl\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image1-1.jpg\",\"datePublished\":\"2023-02-06T17:14:43+00:00\",\"dateModified\":\"2023-05-15T17:51:36+00:00\",\"description\":\"Konfigurujemy po\u0142\u0105czenie panelu Astraada HMI ze sterownikami Emerson VersaMax, z wykorzystaniem portu Ethernet oraz portu szeregowego RS-232.\",\"breadcrumb\":{\"@id\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/#breadcrumb\"},\"inLanguage\":\"pl-PL\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/\"]}]},{\"@type\":\"ImageObject\",\"inLanguage\":\"pl-PL\",\"@id\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/#primaryimage\",\"url\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image1-1.jpg\",\"contentUrl\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image1-1.jpg\",\"width\":1131,\"height\":274},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Produkty ASTOR\",\"item\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/category\/dla-uzytkownikow-produktow-astor\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"Komunikacja paneli Astraada HMI ze sterownikami Emerson serii VersaMax\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/#website\",\"url\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/\",\"name\":\"Poradnik Automatyka\",\"description\":\"Poradnik Automatyka to przydatne kursy, u\u017cyteczne artyku\u0142y i merytoryczne webinary dla ka\u017cdego automatyka i elektryka.\",\"publisher\":{\"@id\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/#organization\"},\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"pl-PL\"},{\"@type\":\"Organization\",\"@id\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/#organization\",\"name\":\"ASTOR\",\"url\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/\",\"logo\":{\"@type\":\"ImageObject\",\"inLanguage\":\"pl-PL\",\"@id\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/#\/schema\/logo\/image\/\",\"url\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/08\/ASTOR_zwykly_sam_logotyp.png\",\"contentUrl\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/08\/ASTOR_zwykly_sam_logotyp.png\",\"width\":3322,\"height\":1078,\"caption\":\"ASTOR\"},\"image\":{\"@id\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/#\/schema\/logo\/image\/\"}},{\"@type\":\"Person\",\"@id\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/#\/schema\/person\/7029e2ba4cc4e4e1c9bfd3b6a47a8b67\",\"name\":\"Mateusz Fas\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"pl-PL\",\"@id\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/#\/schema\/person\/image\/\",\"url\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/04\/M.-Fas.jpg\",\"contentUrl\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/04\/M.-Fas.jpg\",\"caption\":\"Mateusz Fas\"},\"description\":\"Absolwent Mechaniki i Budowy Maszyn na AGH. Absolwent Zarz\u0105dzania i In\u017cynierii Produkcji. W ASTOR aktualnie zajmuje si\u0119 opiek\u0105 nad produktami z oferty Astraada HMI oraz PC.\",\"sameAs\":[\"www.linkedin.com\/in\/mateusz-fas-38a6631a3\/\"],\"url\":\"https:\/\/www.astor.com.pl\/poradnikautomatyka\/autor\/mateuszf\/\"}]}<\/script>\r\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"Komunikacja paneli Astraada HMI ze sterownikami Emerson serii VersaMax | Poradnik Automatyka","description":"Konfigurujemy po\u0142\u0105czenie panelu Astraada HMI ze sterownikami Emerson VersaMax, z wykorzystaniem portu Ethernet oraz portu szeregowego RS-232.","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/","og_locale":"pl_PL","og_type":"article","og_title":"Komunikacja paneli Astraada HMI ze sterownikami Emerson serii VersaMax | Poradnik Automatyka","og_description":"Konfigurujemy po\u0142\u0105czenie panelu Astraada HMI ze sterownikami Emerson VersaMax, z wykorzystaniem portu Ethernet oraz portu szeregowego RS-232.","og_url":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/","og_site_name":"Poradnik Automatyka","article_published_time":"2023-02-06T17:14:43+00:00","article_modified_time":"2023-05-15T17:51:36+00:00","og_image":[{"width":1131,"height":274,"url":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image1-1.jpg","type":"image\/jpeg"}],"author":"Mateusz Fas","twitter_card":"summary_large_image","twitter_misc":{"Napisane przez":"Mateusz Fas","Szacowany czas czytania":"6 minut"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/#article","isPartOf":{"@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/"},"author":{"name":"Mateusz Fas","@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/#\/schema\/person\/7029e2ba4cc4e4e1c9bfd3b6a47a8b67"},"headline":"Komunikacja paneli Astraada HMI ze sterownikami Emerson serii VersaMax","datePublished":"2023-02-06T17:14:43+00:00","dateModified":"2023-05-15T17:51:36+00:00","mainEntityOfPage":{"@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/"},"wordCount":761,"commentCount":0,"publisher":{"@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/#organization"},"image":{"@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/#primaryimage"},"thumbnailUrl":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image1-1.jpg","keywords":["Astraada HMI Panel","VersaMax"],"articleSection":["Produkty ASTOR"],"inLanguage":"pl-PL","potentialAction":[{"@type":"CommentAction","name":"Comment","target":["https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/#respond"]}]},{"@type":"WebPage","@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/","url":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/","name":"Komunikacja paneli Astraada HMI ze sterownikami Emerson serii VersaMax | Poradnik Automatyka","isPartOf":{"@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/#website"},"primaryImageOfPage":{"@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/#primaryimage"},"image":{"@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/#primaryimage"},"thumbnailUrl":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image1-1.jpg","datePublished":"2023-02-06T17:14:43+00:00","dateModified":"2023-05-15T17:51:36+00:00","description":"Konfigurujemy po\u0142\u0105czenie panelu Astraada HMI ze sterownikami Emerson VersaMax, z wykorzystaniem portu Ethernet oraz portu szeregowego RS-232.","breadcrumb":{"@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/#breadcrumb"},"inLanguage":"pl-PL","potentialAction":[{"@type":"ReadAction","target":["https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/"]}]},{"@type":"ImageObject","inLanguage":"pl-PL","@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/#primaryimage","url":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image1-1.jpg","contentUrl":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/02\/image1-1.jpg","width":1131,"height":274},{"@type":"BreadcrumbList","@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/komunikacja-paneli-astraada-hmi-ze-sterownikami-emerson-serii-versamax\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Produkty ASTOR","item":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/category\/dla-uzytkownikow-produktow-astor\/"},{"@type":"ListItem","position":2,"name":"Komunikacja paneli Astraada HMI ze sterownikami Emerson serii VersaMax"}]},{"@type":"WebSite","@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/#website","url":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/","name":"Poradnik Automatyka","description":"Poradnik Automatyka to przydatne kursy, u\u017cyteczne artyku\u0142y i merytoryczne webinary dla ka\u017cdego automatyka i elektryka.","publisher":{"@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/#organization"},"potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"pl-PL"},{"@type":"Organization","@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/#organization","name":"ASTOR","url":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/","logo":{"@type":"ImageObject","inLanguage":"pl-PL","@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/#\/schema\/logo\/image\/","url":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/08\/ASTOR_zwykly_sam_logotyp.png","contentUrl":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2018\/08\/ASTOR_zwykly_sam_logotyp.png","width":3322,"height":1078,"caption":"ASTOR"},"image":{"@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/#\/schema\/logo\/image\/"}},{"@type":"Person","@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/#\/schema\/person\/7029e2ba4cc4e4e1c9bfd3b6a47a8b67","name":"Mateusz Fas","image":{"@type":"ImageObject","inLanguage":"pl-PL","@id":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/#\/schema\/person\/image\/","url":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/04\/M.-Fas.jpg","contentUrl":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-content\/uploads\/2023\/04\/M.-Fas.jpg","caption":"Mateusz Fas"},"description":"Absolwent Mechaniki i Budowy Maszyn na AGH. Absolwent Zarz\u0105dzania i In\u017cynierii Produkcji. W ASTOR aktualnie zajmuje si\u0119 opiek\u0105 nad produktami z oferty Astraada HMI oraz PC.","sameAs":["www.linkedin.com\/in\/mateusz-fas-38a6631a3\/"],"url":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/autor\/mateuszf\/"}]}},"_links":{"self":[{"href":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-json\/wp\/v2\/posts\/15555","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-json\/wp\/v2\/users\/50"}],"replies":[{"embeddable":true,"href":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-json\/wp\/v2\/comments?post=15555"}],"version-history":[{"count":1,"href":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-json\/wp\/v2\/posts\/15555\/revisions"}],"predecessor-version":[{"id":17751,"href":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-json\/wp\/v2\/posts\/15555\/revisions\/17751"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-json\/wp\/v2\/media\/15560"}],"wp:attachment":[{"href":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-json\/wp\/v2\/media?parent=15555"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-json\/wp\/v2\/categories?post=15555"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.astor.com.pl\/poradnikautomatyka\/wp-json\/wp\/v2\/tags?post=15555"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}